Fire Door Inspections

Assessing the Condition of Fire Doors, Identifying Compliance Issues and Establishing a Clear Route to Improvement.

Project Overview

OMNIA Building Consultancy oversaw a fire door inspection project at a school in Durham, coordinating the specialist assessment of 114 fire doors across the school premises.

The project aimed to establish a clear understanding of the condition and performance of the school’s fire doors, identify areas requiring remedial attention and provide recommendations to support the school’s wider fire safety objectives.


Working with a specialist provider, OMNIA oversaw the assessment process and reviewed the findings, which highlighted concerns relating to fire door certification, door condition, seals, glazing and self-closing mechanisms. The inspection also identified the need for a comprehensive fire strategy to support the school’s fire safety arrangements.


Project Objectives

OMNIA's role was to oversee the project and coordinate the specialist inspection, ensuring that the findings provided a clear understanding of the condition of the school's fire doors.


The key objectives were to:

  • Establish the condition and apparent performance of the school's 114 fire doors.

  • Identify defects and potential issues affecting fire and smoke protection.

  • Highlight where certification or supporting documentation was unavailable.

  • Identify priorities for remedial works and further investigation.

  • Consider the wider fire safety requirements of the school, including the need for a comprehensive fire strategy.


Project Execution

Scope of Works

The inspection was undertaken in the corridors, stairwells, offices, changing rooms, kitchens, stores, the sports hall and teaching and support areas.


The inspection considered several aspects of each door's condition and performance, including:

  • The condition and integrity of door leaves and frames.

  • Evidence of fire door certification and supporting test documentation.

  • Door operation and self-closing mechanisms.

  • The condition and presence of intumescent and smoke seals.

  • Hinges, hardware and gaps around the door and frame.

  • Glazing and associated side panels.


OMNIA coordinated the project and considered the specialist inspection findings to establish the issues requiring attention and the recommendations for the next stages of the project.

Key Findings & Recommendations

A number of concerns were identified regarding the certification and fire-resistance performance of the existing doors.


Fire Door Certification

A significant finding was that many of the inspected doors appeared not to be fire-rated, or that sufficient supporting evidence was unavailable to confirm their fire-resistance rating in their current configuration. Some doors also appeared to have replacement leaves fitted into existing frames.


Door Condition and Performance

Defects were identified in a number of areas, including damaged frames, missing or inadequate intumescent and smoke seals, excessive gaps and doors that did not reliably self-close. These issues could affect the doors' ability to provide the intended level of fire and smoke protection.


Glazing and Compartmentation

Concerns were also identified with certain glazed elements, including the suitability of glazing products and associated seals. These areas required further consideration to establish whether the required fire-resistance performance could be demonstrated.


Fire Strategy

The inspection also highlighted that a written fire strategy and supporting drawings were not available at the time of the assessment. A comprehensive fire strategy was recommended to help establish the school's wider fire safety requirements.


Challenges & Solutions

Lack of Certification & Supporting Evidence

One of the key challenges was the lack of supporting certification and test evidence for a number of the existing fire doors. Without this information, their intended fire-resistance performance could not be confirmed.

The specialist inspection identified where evidence was unavailable and recommended replacement with appropriately certified FD30(S) door-sets where required.


Existing Door Defects

The inspection identified a range of defects affecting the condition and operation of the doors, including damaged frames, inadequate seals and problems with self-closing mechanisms.

The findings provided a clear record of the issues requiring attention, allowing the school and project team to consider and prioritise the necessary remedial works.


Wider Fire Safety Documentation

The absence of a documented fire strategy presented a further challenge in understanding the school's overall fire safety arrangements.

A comprehensive fire strategy, prepared with reference to relevant guidance including BB100: Design for Fire Safety in Schools, was recommended to support the school's future fire safety planning.


Client Outcome

OMNIA helped establish a clear understanding of the school's fire door provision and the issues requiring further attention.


The specialist inspection provided a detailed record of the condition of the fire doors, identifying areas where certification, repairs or replacement may be required. The recommendations also highlighted the importance of developing a comprehensive fire strategy to support the school's wider fire safety arrangements.


The findings provided the school and project team with a structured basis for prioritising remedial works, addressing documentation gaps and planning the next steps towards improving fire safety across the premises.